Sizing & runtime
Battery Capacity Calculator (Ah)
Find the nominal amp-hour capacity you need to run a load for a given time, accounting for usable depth of discharge and inverter/conversion losses.
Formula
Wh = P × t ÷ η
Ah(usable) = Wh ÷ V
Ah(nominal) = Ah(usable) ÷ DoD
Worked example
100 W for 5 h on 12 V, 50% DoD, 90% efficiency → 555.6 Wh → 46.3 Ah usable → 92.6 Ah nominal.
Limitations and warnings
- Rated Ah is normally specified at the 20-hour rate (C20). Higher currents deliver less capacity (Peukert effect) in lead-acid batteries.
- Cold temperatures and ageing reduce available capacity; add a margin.
- This sizes energy storage only. It does not determine starting (CCA) requirements.
Four values that are often confused
- Nominal capacity (Ah)
- Charge a battery delivers under rated conditions, usually over 20 hours (C20) at 25 °C.
- Usable capacity
- The part of the nominal capacity you can use without damaging the battery — about 50% for lead-acid, 80–90% for LiFePO4.
- Cranking current (CCA)
- Current deliverable for a short time in the cold to start an engine. It measures power, not stored charge, and cannot be converted to Ah.
- Stored energy (Wh)
- Ah × voltage. The right unit to compare batteries of different voltages.